EdgeX User Manual
中文用户手册 · Product Guide · Architecture
This English manual covers protocols, deployment, day-to-day use, and hot-path best practices. Deep Chinese reference remains in USER_MANUAL.md.
1. Protocols (southbound)
| Protocol | Key | Notes |
|---|---|---|
| Modbus TCP/RTU | modbus-tcp / modbus-rtu / modbus-rtu-over-tcp |
Serial execution; Gap batch read |
| BACnet IP | bacnet-ip |
Scan + object scan |
| OPC UA | opc-ua |
Parallel; subscribe / batch read |
| S7 | s7 |
rack/slot |
| EtherNet/IP | ethernet-ip |
CIP tags |
| Omron FINS | omron-fins |
TCP/UDP |
| SNMP | snmp |
v2c / v3 |
| IEC 104 | iec60870-5-104 |
Interrogation + spontaneous |
| DL/T645 | dlt645 |
Meter DI |
| Mitsubishi SLMP | mitsubishi-slmp |
MC 3E |
| Profinet IO | profinet-io |
Slot IO |
| KNXnet/IP | knxnet-ip |
Group address / discovery |
| EtherCAT | ethercat |
PDO/SDO (M1) |
Driver docs: index_en.
2. Installation
Requirements
| Minimum | Recommended | |
|---|---|---|
| RAM | 128MB | 512MB+ |
| Disk | 1GB | 4GB+ |
| CPU | 1 core | 2+ |
Packages
# Debian/Ubuntu
sudo dpkg -i edgex-v{version}-amd64.deb
# RHEL/Fedora
sudo rpm -ivh edgex-v{version}-amd64.rpm
sudo systemctl enable --now edgex
Open http://<host>:<port>. First boot runs the install wizard if data/config.db is missing.
Source build: see README.en.md.
3. Operations (shadow-centric)
- Create channel → choose protocol → set connection params
- Add device + points → set interval / Scan Class
- Enable channel → ScanEngine registers tasks
- Verify live values in UI (WebSocket from ShadowCore)
- Optional: virtual shadow formulas, edge rules, northbound MQTT/OPC UA/Sparkplug
- Watch SLA:
GET /api/diagnostics/scan-engine
Data path:
Driver ReadPoints → ShadowIngress → ShadowCore → UI / Edge / History / Northbound
4. Best practices
| Do | Don’t |
|---|---|
| Keep intervals realistic for the bus (especially Modbus RTU) | Flood Serial buses with 10ms polls on dozens of slaves |
| Use Scan Class (fast/normal/slow) for mixed criticality | Put all tags in one ultra-fast class |
| Map northbound from shadow tags | Bypass shadow with ad-hoc driver callbacks |
Check sla_warnings and circuit-breaker state |
Ignore Dead/Offline devices forever without cooldown |
| Enable northbound cache for weak networks | Assume always-on uplink |
Architecture detail: Architecture Overview.
5. Troubleshooting quick list
| Symptom | Check |
|---|---|
| No live values | Channel enabled? Driver Connect? Shadow populated? |
| High lag / miss | diagnostics API; per-device CB; backpressure |
| Illegal Modbus address | Point enters long SKIPPED cooldown (24h) |
| Northbound silent | Pipeline handlers registered? Client connected? Cache full? |